Where should the Electrostatic Precipitator (ESP) be placed: near the hood or near the fan?

Can the installation position of the Electrostatic Precipitator (ESP) affect its efficiency

Standard guidelines for the installation location of kitchen exhaust purifiers: I. Optimal Solution:

Install near the exhaust hood (after a short, straight duct section from the hood outlet), in the sequence of Purifier → Fan. Key reasons:

**Highest purification efficiency due to high fume temperature and un-condensed grease**

Fumes exiting the hood are hot, with grease present as gaseous droplets or mist. If they pass through a long duct first, the grease condenses and adheres to the inner walls, forming thick, heavy deposits; this drastically increases the load on the purifier and creates a risk of short-circuits or fires.

**Protects the fan and significantly reduces cleaning and maintenance costs**

By passing fumes through the purifier first, the vast majority of grease is captured; clean air then enters the fan, leaving the impeller and housing virtually free of grease and eliminating the risk of fire caused by grease accumulation.

**Less grease in the ductwork and lower fire risk**

Only purified air flows through the ducts, resulting in very slow grease accumulation on the walls and making it easier to pass annual fire safety inspections.

**Installation spacing requirements:** Install the purifier after a straight duct section of 0.5–1 meter from the hood outlet. This prevents turbulent airflow from the hood from directly impacting the purification plates, ensuring uniform airflow. II. Not Recommended: Installing the purifier downstream of the fan (Fan → Purifier). Disadvantages:

The entire duct section is filled with high-concentration fumes, leading to rapid grease buildup on the walls and creating a severe fire hazard;

The fan directly inhales unpurified, concentrated fumes, causing heavy grease adhesion on the impeller; this disrupts the fan's dynamic balance and increases noise, while long-term exposure to hot, greasy deposits creates a risk of ignition;

The fan creates negative pressure, making the purifier prone to internal airflow short-circuiting; some fumes bypass the purification zone and are exhausted directly, resulting in substandard purification and a high likelihood of failing environmental compliance tests. III. Supplementary Notes for Special Operating Conditions

**Limited space; inability to install the purifier directly beneath the hood**

The upstream ductwork may be shortened to position the unit as close to the hood as possible; installing the purifier at the end of an excessively long exhaust duct is prohibited.

**High negative pressure from centrifugal fans; excessively long ductwork**

The purifier must be installed upstream; fire dampers must be installed in the ductwork, and regular duct cleaning is required.

**Specific requirements for electrostatic precipitators (ESPs)**

Electrostatic units are susceptible to damage from high-volume liquid oil droplet impingement; it is recommended to install a flow-equalizing screen or oil baffle at the hood outlet before the air enters the purifier.

**Concise summary of integrated engineering, environmental, and fire safety standards:

 

** Install the Fume Purifier (ESP) close to the hood. Sequence: Hood → Fire Damper → Fume Purifier (ESP) → Fan → High-level Discharge Duct.

 

 

DR. AIRE Electrostatic Precipiotator comes with UL listed, CE, RoHS, ASHRAE 52.2-2017 certificates. We help our clients/agents all over the world to set up business! Contact us for free quote now!

 

If you have same problem,  please contact DR. AIRE Electrostatic Filter Manufacturer for trouble shooting!

prev
Does an Electrostatic Precipitator generates ozone during operation
recommended for you
GET IN TOUCH WITH Us

ABOUT RUIHE (DR. AIRE)

Dongguan Ruizhaohe Environmental Protection Equipment Co., Ltd

We are specializing in the design, production and after-sales service of fume purification

equipment and exhaust gas treatment equipment.

 


ONE-STOP AIR CLEANING MANAGEMENT SOLUTIONS


(1) - Commercial cooking fume odour management

(2) - Industrial exhaust management

(3) - CNC machines oil mist management

CONTACT US

Tel:86 - 0769 -  23667212    Fax:86 - 0769 - 27285034

 

E-mail:sales04@RUIHEetech.com

Adderss:Bajiaowo Industrial Zone, Wanjing District, DongguanCity, Guangdong Province, China

 

 

Follow Us & Like Us

Copyright © 2026 www.draire.net | Sitemap Privacy Policy
Customer service
detect